COMPARABILITY OF THERMAL AND ELECTRICAL DAMAGE WITH GAS RATIOS IN CHROMATOGRAPHIC ANALYSIS OF OIL POWER TRANSFORMERS

dc.contributor.authorKhamrakulova Khilola Abdurashidovna
dc.contributor.authorYusupov Dilmurod Turdaliyevich
dc.date.accessioned2025-12-29T18:16:56Z
dc.date.issued2025-06-13
dc.description.abstractThe article presents an in-depth study of the comparability of thermal and electrical damage to oil-filled power transformers with gas ratios obtained by chromatographic dissolved gas analysis (CDGA). Particular attention is paid to the analysis of the formation mechanisms of key gases (C₂H₂, C₂H₄, CH₄, H₂, CO, CO₂) and their ratios under conditions of various types of defect formation: partial discharges, arc discharges and local overheating. Taking into account the uncertainty and overlapping of diagnostic boundaries, the need to use fuzzy logic methods and probabilistic models (in particular, Bayesian analysis) for a more reliable interpretation of gas signs is substantiated. Based on a generalization of experimental data and regulatory recommendations (including IEEE C57.104–2019 and IEC 60599), an improved approach to determining the nature of defects in the early stages of their development, including in the presence of multifactorial damage, is proposed.
dc.formatapplication/pdf
dc.identifier.urihttps://webofjournals.com/index.php/4/article/view/4582
dc.identifier.urihttps://asianeducationindex.com/handle/123456789/25470
dc.language.isoeng
dc.publisherWeb of Journals Publishing
dc.relationhttps://webofjournals.com/index.php/4/article/view/4582/4537
dc.rightshttps://creativecommons.org/licenses/by-nc-nd/4.0
dc.sourceWeb of Technology: Multidimensional Research Journal; Vol. 3 No. 6 (2025): WOT; 30-37
dc.source2938-3757
dc.subjectPower transformer; chromatographic dissolved gas analysis (CDGA); thermal damage; electrical discharges; gas indices; gas ratios; partial discharges; overheating; fuzzy logic; Bayesian method; diagnostics; IEEE C57.104; IEC 60599; combined defects; express analysis.
dc.titleCOMPARABILITY OF THERMAL AND ELECTRICAL DAMAGE WITH GAS RATIOS IN CHROMATOGRAPHIC ANALYSIS OF OIL POWER TRANSFORMERS
dc.typeinfo:eu-repo/semantics/article
dc.typeinfo:eu-repo/semantics/publishedVersion
dc.typePeer-reviewed Article

item.page.files

item.page.filesection.original.bundle

pagination.showing.labelpagination.showing.detail
loading.default
thumbnail.default.alt
item.page.filesection.name
abdurashidovna_2025_comparability_of_thermal_and_electrical.pdf
item.page.filesection.size
478.83 KB
item.page.filesection.format
Adobe Portable Document Format

item.page.collections